Sensortech

Fire Sprinklers

Concealed Sprinklers

Concealed Sprinklers

Operation

During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches. Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand and the bulb to shatter, releasing the bulb cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguised or control the fire.

Category

Concealed Type Sprinkler
The sprinkler is pre-assembled with a threaded adapter for installation with a low-profile cover assembly that provides up to 10mm of vertical .

Parameter Specification
Sprinkler Type
Temperature Rating 68°C (155°F) / 93°C (200°F)
Connection Screw Size NPT 1/2″
Minimum Working Pressure 7 psi (0.0483 MPa)
Maximum Working Pressure 175 psi (1.23 MPa)
Discharge Coefficient K = 5.6 GPM/psi¹ᐟ² (80.7 LPM/bar¹ᐟ²)